Root Cause of Bearing Currents and Mitigation Strategies –

Bearing NewsOct 10, 2026

Electrical discharge machining (EDM) damage caused by inverter-driven motors has become one of the most dominant failure modes in modern rotating equipment. During his presentation “Root Cause of Bearing Currents and Mitigation Strategies” at the Bearing & Power Transmission Forum, reliability specialist Mark Gurney of 3PHI Reliability explained how pulse-width modulation (PWM) drives generate high-frequency common mode currents that attack bearings, lubrication systems, and motor insulation.

With more than 10,000 motor tests conducted since 1997, Gurney has observed a clear trend: inverter-related bearing damage is no longer an exception, it is a systemic issue across industries increasingly relying on variable speed drives (VSDs). While drives improve energy efficiency and process control, they introduce high-frequency switching events that create reflective voltages, capacitive coupling, and circulatory currents inside motors.

These electrical phenomena manifest in several destructive ways:

  • Grease degradation and conductive lubricant formation
  • Electrical fretting and bearing fluting
  • Insulated bearing breakdown
  • Accelerated motor winding insulation failure

Contrary to common belief, installing insulated bearings or shaft grounding brushes is not a universal solution. Each mitigation strategy addresses only specific types of bearing currents. Without proper measurement and root cause identification, incorrect solutions may accelerate failure rather than prevent it.

Using tools such as Rogowski coils to measure common mode current, rather than relying solely on shaft voltage readings, allows engineers to quantify peak-to-peak bearing current and determine risk thresholds. Research indicates that exceeding approximately 0.5 amps per square millimetre of bearing contact area significantly increases the likelihood of fluting damage. For example, a 200 kW motor may reach a critical initiation level at around 12 amps peak-to-peak.

The presentation further highlighted the impact of impedance imbalance, magnetic asymmetry, grounding resistance, rotor defects, and improper cable shielding, all contributing to circulatory current and EDM erosion. Data analysis across hundreds of motors confirms a strong correlation between impedance imbalance and premature failure rates, particularly in inverter-driven applications.

Continue the conversation on reliability, maintenance excellence, and industry best practices at the Bearing & Power Transmission World Meetings 2027 in Belgrade. Join global experts, manufacturers, and distributors to explore the strategies shaping the future of our industry.

Visit www.bearing-power.com and secure your place.

B&P2024 B&P2024

Source: Bearing News

By Bearing News · Bearing design & application specialists

This article is prepared by the SINO BEARINGS (Sinoti Tech) engineering team, based on published bearing standards (ABEC / ISO P0–P2), material datasheets, and field application experience across industrial, food, medical and aerospace uses. For manufacturer background, certifications and facilities, see our About page.